Flow Control - Actuator

Home > Flow Control Products > Actuation > EFMB-1/2/3 Series

EFMB-1/2/3 Series Intergral Type Small Quarter Turn Electric Actuator

The EOM series electric actuator is a type of motor that uses a multi-stage reduction gear, worm gear, and other mechanisms to generate rotational force. This force is then transmitted through the output shaft to switch valve devices by rotating them 90°. The actuator is mainly used to control the opening angle of valves, such as butterfly valves, ball valves, plug valves, etc. The EOM integral type has a torque range of 10-20000N.m, and the conventional electric actuator in the series operates without a clutch, making it durable and reliable. It has a stable stroke and effectively improves transfer efficiency.

TECHNICAL DATA
Ambient Temperature-25°C…..70 °C; Optional: -40°C…..60 °C
Ingress ProtectionIP67, Optional: IP68 ( Maximum 7m; Max: 72 hours)
Torque Range10-30N.m
Applicable Voltage1 phase:AC/DC24V / AC110V / AC220V / AC230V /AC240V
EFMB-1/2/3 SERIES INTRGRAL TYPE SMALL QUARTER TURN ELECTRIC ACTUATOR
Material of Actuator BodyAluminum Alloy
Control ModeOn-off Type & Modulating Type
Torque Range10-30N.m
Running Time11-13s
Applicable Voltage1 phase:AC/DC24V / AC110V / AC220V / AC230V /AC240V
Ambient Temperature-25°C…..70 °C; Optional: -40°C…..60 °C
Anti-vibration LevelJB/T8219
Noise LevelLess than 75 dB within 1m
Ingress ProtectionIP67, Optional: IP68( Maximum 7m; Max: 72 hours)
Connection SizeISO5211
Motor SpecificationsClass F, with thermal protector up to +135°C(+275°F); Optional : Class H
On/off Type SignalInput Signal: AC/DC 24 input control or AC 110/220v input control
Signal Feedback:
1. Close the valve contact
2. Open the valve contact
3. Optional: Closing torque signal contact Local/ remote contacts
4. Integrated fault contact 4~20 mA to send
Malfunction Feedback: Integrated fault alarm; Motor overheating
Optional: Undercurrent protection contact
Modulating Type SignalInput Signal: 4-20mA; 0-10V: 2-10V
Input impedance: 250Ω (4-20mA
Output signal: 4-20mA; 0-10V: 2-10V
Output impedance: ≤ 750Ω (4-20mA) Repeatability and linearity within ±1% of full valve stroke
Signal Reverse: Support
Loss Signal Mode Setting: Support
Dead Zone: ≤2.5%
Working SystemOn-off Type: S2-15 min, no more than 600 times per hour start Modulating Type: S4-50% up to 600 times per hour start; Optional: 1200 times per hour
IndicationIndicator of pointer
Other Function1. Phase correction (3-phase power supply only)
2. Torque protection
3. Motor overheat protection
4. Moisture - resistant heaters (anti-moisture device)

Do you need to know more information about this product?